Case Study (Corporate Headquarters)
Cable & Component
System
The technology cable plant includes Voice, Data, Audio Visual, Building Security, CATV (Cable TV), and Sound Masking. Converge IP Technology is the cable consultant on the project. The selected cable and component vendors are Belden and Panduit respectively. The Audio/Video System consists of 8 fixed and 3 potable VTC units. The VTC systems are H. 3.23 (IP) with support for ISDN BRIs. Cable TV (CATV) is routed through the adjcent building up to the Technology Center via a hard-line ½” coax cable. The cable is terminated on the VDH (Video Distribution Hub). Horizontal CATV distribution is done via standard station Cat5e cable. The south IDF closets will house the CCTV terminations and the north IDF closets will contain the Data Gathering Panels (DGP) for the card readers. The South IDF room will also contain the CATV riser as well. IDF Closet Systems ·
Two IDF closets per
floor (North & South) ·
IDF closets are vertically
stacked with minor exceptions due to narrowing in upper stack. ·
Closets average about 80 sq.
ft. · Each IDF closet will contain voice, video, building security & data station and riser cabling ·
Building security Data Gathering
Panel (DGP) ·
CATV Distribution Hub
·
Sound Masking equipment ( North
IDF closet only on one floor).
·
Four (4) floor mounted racks, one
of which is for expansion.
·
Each rack will have a rack
mounted UPS with two (2) 30 amps & one 20 amp general rack mounted
circuits.
·
The cable/component vendor is
Belden/Panduit.
·
Each IDF closet will be
Air-conditioned.
·
Each IDF
closet will have card-key access. IDF Rack Terminations
IDF Wall Field
Terminations
Riser
Terminations
Technology Center
Terminations
Typical
Workstation
Terminations
Workstation Standards
PATCH PANELS
48-PORT UTP
PATCH PANELS
Description: 48-port Category-5e rack-mounted
patch panels with 110-type connector blocks and strain relief brackets in the
back. Patch panels shall be wired according to TIA 568B. All patch panels shall
provide space for a label for each port both in the front and the back. Purpose:
To terminate data outlet and wallfield tie cables in the TR’s. To terminate tie cables in the Data
Center and other technology spaces within.
24-PORT UTP PATCH
PANELS
Description: 24-Port Category-5e rack-mounted
patch panels with 110-type connector blocks and strain relief brackets in the
back. Patch panels shall be wired according to TIA 568B. All patch panels shall
provide space for a label for each port both in the front and the back. Purpose:
To terminate tie cable for LAN racks and cabinets in Data Center and
36th Floor North TR.
Used for termination of A/V floor-to-floor risers in TR’s.
24-PORT FIBER OPTIC DISTRIBUTION
CENTER
Description: 24-port fiber optic termination
center loaded with two (2) 12-port multi-mode duplex SC coupler panels where
required. Takes up 1RU of vertical
rack space and supports two (2) coupler panels. Purpose: To terminate fiber optic tie cables in
server cabinets within the Data Center, and technology spaces.
48-PORT FIBER OPTIC DISTRIBUTION
CENTER
Description: 48-port fiber optic
termination center with two (2) 12-port single-mode duplex SC coupler panels,
one (1) 12-port multi-mode duplex coupler panels and one (1) blank panel. Takes up 2RU of vertical rack space and
supports 4 coupler panels. Purpose: To terminate fiber optic backbone cables
in TRs where cross-floor tie cables are not required.
72-PORT FIBER OPTIC DISTRIBUTION
CENTER
Description: 72-port fiber optic
termination center with three (3) 12-port single-mode duplex S Purpose: to terminate fiber optic backbone cables in TRs on typical floors where cross-floor tie cables are required.
144-PORT FIBER OPTIC DISTRIBUTION
CENTER
Description: 144-port fiber optic
termination center loaded with multi-mode or single-mode coupler panels as
applicable. Blank panels shall
occupy all open or unused coupler panel spaces. Takes up 4RU of vertical rack space and
supports twelve (12) coupler panels. Purpose: For termination of fiber optic backbone
cables at the MC in Technology Center.
For termination of fiber optic tie cables distributed to technology
spaces within the Data Center.
VOICE RISER
BLOCKS
Description: 300-pair 110-type
block field termination kit with white labels and clear covers for TRs and MDF. Termination blocks at IDF’s in
TR’s shall have legs for wall mounting.
Termination blocks at MDF will be rack mounted and will not have
legs Purpose: To terminate voice riser cables in TRs
and MDF.
VOICE DISTRIBUTION
BLOCKS
Description: 300-pair 110-type block field
termination kit with blue labels and clear covers. Purpose: To terminate voice distribution cables
in IDF closets.
TIE CABLE
BLOCKS
Description: 300-pair 110-type block field
termination kit with gray labels, yellow labels and clear covers. Purpose:
To terminate rack to wall-field tie cables in TRs using yellow
labels. To terminate cross-floor
tie cables using gray labels.
MDF TIE CABLE
BLOCKS
Description: 300-pair 110-type
block field termination kit with green labels and clear covers. Purpose: To terminate MDF to
Telco wall tie cables in Data Center for extending Telco/Carrier circuits to
voice MDF.
EQUIPMENT
RACKS AND FRAMES
RACKS
Description: Universal 19”, self-supporting 7'-0" high rack with
10/32 taped EIA hole pattern. This rack will provide vertical cable management
channels. It shall be black in color. Install cable management rings as provided
by manufacturer.
Purpose: Supporting LAN hardware and patch
panels in IDF closets and Communication Center and to provide adequate
patch-cord management.
MDF DOUBLE SIDED FLOOR
FRAME
Description: Double sided frame with mounting
brackets for 110 blocks. Each side
of rack shall support 3600 pairs, or 12 300 pair blocks. Frame shall provide cable management
bars for managing cross-connect.
Lowest block position shall be 18” off the floor. Purpose: For supporting all riser
and PBX termination block and provide management of cross-connect wires
SERVER
CABINETS
Description: Equipment cabinets(s) will be 7-foot x
24-inch with 19-inch rails. Cabinets shall be supplied with necessary cage nuts
and screws. Cabinets shall be adjoined, have end panels at the ends of each row
and shall be properly grounded. Each Cabinet will have two (2) 30-amps-110-volt
Power Distribution Units (PDU), and a top mounted fan kit.
Purpose: To house servers and other active equipment, support patch panels and cable management.
|